• DocumentCode
    483147
  • Title

    On-line monitoring and study of transformer DC bias

  • Author

    Hailiang, Lu ; Xishan, Wen ; Xiaoping, Li ; Xuefang, Tong

  • Author_Institution
    Sch. of Electr. Eng., Wuhan Univ., Wuhan
  • fYear
    2008
  • fDate
    17-20 Oct. 2008
  • Firstpage
    4313
  • Lastpage
    4316
  • Abstract
    Basing on virtual instrument model, a suit of system was designed for monitoring DC bias of transformer. The monitoring system can measure the DC current through transformer neutral using Hall current sensor, the vibration of transformer oil tank using piezoelectric acceleration sensor, the noise of transformer using capacitive acoustic sensor. The software was developed on LabVIEW. The system was used to monitor the main transformer of a 500 kV substation.
  • Keywords
    DC transformers; power system measurement; DC current measurement; Hall current sensor; capacitive acoustic sensor; on-line monitoring; piezoelectric acceleration sensor; transformer DC bias; transformer neutral; virtual instrument; Acoustic measurements; Acoustic sensors; Capacitive sensors; Current measurement; Instruments; Monitoring; Noise measurement; Oil insulation; Sensor systems; Vibration measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Machines and Systems, 2008. ICEMS 2008. International Conference on
  • Conference_Location
    Wuhan
  • Print_ISBN
    978-1-4244-3826-6
  • Electronic_ISBN
    978-7-5062-9221-4
  • Type

    conf

  • Filename
    4771551