DocumentCode
483171
Title
The calculation of ampere force on electric power transformer under the short circuit situation
Author
Jiao, Liyang ; Bai, Baodong ; Li, Hongyou
Author_Institution
Sch. of Electr. Eng., Shenyang Univ. of Technol., Shenyang
fYear
2008
fDate
17-20 Oct. 2008
Firstpage
4423
Lastpage
4426
Abstract
Based on the finite element analysis, the leakage magnetic field and the short circuit force of SFPZ-180000 kVA power transformer under the short circuit in the low voltage winding are calculated. The distributions of the leakage magnetic field and the short circuit force in low voltage windings and high voltage windings are analyzed in three different conditions when the power transformer is under rated tap, maximum tap and minimum tap. Furthermore, the compressive stress of the supporting block between the low voltage wire pies at different positions is also calculated.
Keywords
finite element analysis; magnetic fields; power transformers; transformer windings; SFPZ-180000 kVA power transformer; ampere force calculation; compressive stress; electric power transformer; finite element analysis; leakage magnetic field; low voltage winding; short circuit situation; Boundary conditions; Electromagnetic fields; Electromagnetic forces; Electromagnetic transients; Finite element methods; Low voltage; Magnetic analysis; Magnetic circuits; Magnetic fields; Power transformers;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Machines and Systems, 2008. ICEMS 2008. International Conference on
Conference_Location
Wuhan
Print_ISBN
978-1-4244-3826-6
Electronic_ISBN
978-7-5062-9221-4
Type
conf
Filename
4771575
Link To Document