DocumentCode
484868
Title
About the speaker - Clive de Salis
Author
de Salis, Clive
fYear
2008
fDate
9-9 Dec. 2008
Firstpage
1
Lastpage
2
Abstract
BS EN IEC 61511 provides the guidance to Control and Safety Integration and it states: ‘.....Wherever practicable, the safety instrumented functions should be separated from the non-safety instrumented functions.’ ‘.... the basic process control system shall be designed to be separate and independent to the extent that the functional integrity of the safety instrumented system is not compromised.’ ‘.... Adequate independence means that neither the failure of any non-safety functions nor the programming access to the non-safety software functions is capable of causing a dangerous failure of the safety instrumented function‘ If we want to share common items between the safety system and the basic process control system then can we? For new installations can we design for this? For existing installations (called ‘Legacy’ installations) this requirement has often neither been present nor covered properly.
fLanguage
English
Publisher
iet
Conference_Titel
Power Generation Control - Building Flexibility and Sustainability into Plants, 2008 IET 3rd Annual Seminar on
Conference_Location
Birmingham
ISSN
0537-9989
Print_ISBN
978-1-84919-007-7
Type
conf
Filename
4781820
Link To Document