DocumentCode :
488462
Title :
Self Tuning Load Frequency Controller for Interconnected Power Systems Including Effects of Nonlinearities
Author :
Lee, K.A. ; Yee, H.
Author_Institution :
Graduate Student, School of Electrical Engineering, University of Sydney, N.S.W. 2006, Australia
fYear :
1990
fDate :
23-25 May 1990
Firstpage :
2100
Lastpage :
2105
Abstract :
A study is described of the load frequency and tie-line power control of a multi-area interconnected power system, using self tuning control based on a minimum variance strategy. Each area in the interconnection is represented by a stochastic ARMAX model and area generation control is computed by a self tuning algorithm with an extended recursive least squares technique for parameter estimation. It is shown that the ARMAX predictive model, although inadequate in modelling the non-zero mean value of the power system load disturbances, is capable of describing the system dynamic behaviour and satisfies the load frequency control objectives. To comply with the zero-mean characteristic of the ARMAX model, a modified predictive model is developed where the non-zero mean component of the load disturbances is predicted as a function of local area variables, and integrated into the control algorithm. Simulation studies show that with this modification, the system response is noticeably improved especially when generation rate constraint and governor dead-band nonlinearities are taken into account.
Keywords :
Control nonlinearities; Control systems; Frequency; Nonlinear control systems; Power system control; Power system interconnection; Power system modeling; Power systems; Predictive models; Tuning;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
American Control Conference, 1990
Conference_Location :
San Diego, CA, USA
Type :
conf
Filename :
4791100
Link To Document :
بازگشت