DocumentCode :
501976
Title :
A new method to eliminate DG´s negative effects on the existing distribution network protection
Author :
Wang, Hui
Author_Institution :
Shanghai Municipal Electric Power Company of State Grid - China
fYear :
2009
fDate :
8-11 June 2009
Firstpage :
1
Lastpage :
4
Abstract :
Distributed Generation (DG) will affect the amperage, direction and distribution of fault current. With the penetration of DG, the existing protection and automatic devices may not operate correctly. In accordance with how DG affects the protection of distribution system, the importance of connecting a fault current limiter (FCL) to DG to restrict the fault current is analyzed, and the detailed algorithm to get the parameters of FCL is presented with a case. In the end, through the simulation by Matlab/EMTP we proved that FCL with properly selected parameters can effectively restrict DG´s fault current, eliminate DG´s negative effects and guarantee the original protection´s reliability and selectivity. In addition, We can also add direction protection to solve the problem of DG´s backward fault current if necessary.
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution - Part 1, 2009. CIRED 2009. 20th International Conference and Exhibition on
Conference_Location :
Prague, Czech Republic
ISSN :
0537-9989
Print_ISBN :
978-1-84919126-5
Type :
conf
Filename :
5255307
Link To Document :
بازگشت