• DocumentCode
    502054
  • Title

    Effect of dry zone formation around underground power cables on their ratings

  • Author

    Gouda, Ossama E. ; Amer, Ghada M. ; El Dein, Adel Z.

  • Author_Institution
    Cairo University, Egypt
  • fYear
    2009
  • fDate
    8-11 June 2009
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    As it is known there are many factors affecting underground power distribution cables loadings. Such these factors are ambient temperature, cable depth laying, and number of cable parallel circuits and thermal resistivity of the soil. One important factor usually ignored is the formation of dry zones around the underground power cables due to cable loading. Dry zones are usually formed around underground power cables under loading condition due to the migration of soil moisture content. In this paper the effect of dry zone formation on the underground power cables ampacity is investigated. De-rating factor for the formation of dry zone around underground power cables is suggested and calculated for different types of natural backfill soils. IEC 60287-1-3 is taken as reference. Experimental work is done to study the dry zone phenomena of each type of soil.
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution - Part 1, 2009. CIRED 2009. 20th International Conference and Exhibition on
  • Conference_Location
    Prague, Czech Republic
  • ISSN
    0537-9989
  • Print_ISBN
    978-1-84919126-5
  • Type

    conf

  • Filename
    5255465