DocumentCode
502093
Title
Fault current source to ensure the fault level in inverter-dominated networks
Author
Van Overbeeke, Frank
Author_Institution
EMforce B.V. - the Netherlands
fYear
2009
fDate
8-11 June 2009
Firstpage
1
Lastpage
4
Abstract
This paper addresses the issue of ensuring the fault level in inverter-dominated islanded networks. This issue is particularly gaining significance with the advent of microgrids. It is proposed to add one component to the network which supplies the fault current when required and which keeps the network alive long enough for all inverters to resume operation, if they have switched off during the transient. This component is named a Fault Current Source (FCS).