DocumentCode :
502196
Title :
First field experience of on-line partial discharge monitoring of MV cable systems with location
Author :
van der Wielen, Peter ; Steennis, Fred
Author_Institution :
KEMA - the Netherlands
fYear :
2009
fDate :
8-11 June 2009
Firstpage :
1
Lastpage :
4
Abstract :
A new measuring system is presented for the on-line monitoring and location of partial discharges (PDs) in medium-voltage power cables. The system uses two inductive sensors, each at one cable end. The measuring system is called PD-OL, which stands for PD detection Online with Location. A pulse injection system is used for the time synchronization of the data intake at both cable ends and for the on-line calibration. PD data is send via internet to the KEMA Control Center for interpretation and final presentation, made visible on a secured web-site for the network owners. This paper discusses the basics of PD-OL and a number of measurement results.
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution - Part 1, 2009. CIRED 2009. 20th International Conference and Exhibition on
Conference_Location :
Prague, Czech Republic
ISSN :
0537-9989
Print_ISBN :
978-1-84919126-5
Type :
conf
Filename :
5255607
Link To Document :
بازگشت