DocumentCode
502300
Title
The influence of fault type on fault current in MV compensated networks
Author
Toman, Petr ; Dvorak, Jaromir ; Orsagova, Jaroslava ; Topolanek, David
Author_Institution
Brno University of Technology, Czech Republic
fYear
2009
fDate
8-11 June 2009
Firstpage
1
Lastpage
4
Abstract
The paper deals with earth fault phenomena in MV compensated networks. There were damaged concrete towers in E.ON Czech Republic distribution network and the aim of experiment was to measure electrical values during the fault. The experiment was prepared and six types of fault for tuned and untuned Petersen coil and for two distances between busbar and point of fault were subsequently connected. The faults were connected by one-phase load disconnector and the line was in normal operation - loaded.
fLanguage
English
Publisher
iet
Conference_Titel
Electricity Distribution - Part 1, 2009. CIRED 2009. 20th International Conference and Exhibition on
Conference_Location
Prague, Czech Republic
ISSN
0537-9989
Print_ISBN
978-1-84919126-5
Type
conf
Filename
5255712
Link To Document