DocumentCode :
502553
Title :
The criteria for neutral point treatment selection in 20(10) kV radial networks in “Elektra” Zagreb
Author :
Kulis, Ivan Goran ; Boras, Miljenko ; Njavro, Boris ; Vidovic, Filip ; Sagovac, Goran ; Duric, Igor
Author_Institution :
Kon??ar-KET - Croatia
fYear :
2009
fDate :
8-11 June 2009
Firstpage :
1
Lastpage :
4
Abstract :
In the MV network of HEP-ODS “Elektra” Zagreb three ways of substation (transformer) neutral point treatment are used: isolated, low-ohmic grounded and resonant grounded. Methods and results of the study of defining the criteria for appropriate neutral treatment selection are described in this article. Selection criteria consider: • Technical features of all three treatments concerning the earthfault currents, overvoltages and network operation originated from literature, measuring, computer analysis and operation experiences; • People safety requirements and rules (touch voltages), heath and voltage stresses and interferences with telecommunications lines; • Network importance (number and type of connected customers), size (length of galvanic connected lines), type (cable and overhead lines ratio, type of poles, types of cable junctions and screens); • Network reliability (SAIFI and SAIDI); • Earth systems requirements concerning earthfault currents and soil resistivity.
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution - Part 1, 2009. CIRED 2009. 20th International Conference and Exhibition on
Conference_Location :
Prague, Czech Republic
ISSN :
0537-9989
Print_ISBN :
978-1-84919126-5
Type :
conf
Filename :
5255966