• DocumentCode
    502553
  • Title

    The criteria for neutral point treatment selection in 20(10) kV radial networks in “Elektra” Zagreb

  • Author

    Kulis, Ivan Goran ; Boras, Miljenko ; Njavro, Boris ; Vidovic, Filip ; Sagovac, Goran ; Duric, Igor

  • Author_Institution
    Kon??ar-KET - Croatia
  • fYear
    2009
  • fDate
    8-11 June 2009
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    In the MV network of HEP-ODS “Elektra” Zagreb three ways of substation (transformer) neutral point treatment are used: isolated, low-ohmic grounded and resonant grounded. Methods and results of the study of defining the criteria for appropriate neutral treatment selection are described in this article. Selection criteria consider: • Technical features of all three treatments concerning the earthfault currents, overvoltages and network operation originated from literature, measuring, computer analysis and operation experiences; • People safety requirements and rules (touch voltages), heath and voltage stresses and interferences with telecommunications lines; • Network importance (number and type of connected customers), size (length of galvanic connected lines), type (cable and overhead lines ratio, type of poles, types of cable junctions and screens); • Network reliability (SAIFI and SAIDI); • Earth systems requirements concerning earthfault currents and soil resistivity.
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution - Part 1, 2009. CIRED 2009. 20th International Conference and Exhibition on
  • Conference_Location
    Prague, Czech Republic
  • ISSN
    0537-9989
  • Print_ISBN
    978-1-84919126-5
  • Type

    conf

  • Filename
    5255966