DocumentCode :
511048
Title :
Prebreakdown phenomena in CO2/SF6 under very fast transients in non-uniform field
Author :
Pfeiffer, W. ; Kuzishin, N. ; Zhurkov, M.
Author_Institution :
Lab. for Electr. Meas. Tech., Darmstadt Univ. of Technol., Darmstadt, Germany
fYear :
2008
fDate :
7-12 Sept. 2008
Firstpage :
537
Lastpage :
540
Abstract :
The Gas Insulated Line (GIL) is a reliable system for electrical energy transport. One of the important parts of the GIL is the insulating gas that can be stressed not only with lightning impulses, but also with very fast transients (VFT) if a busduct connector is being closed or opened. An alternative gaseous medium is needed in order to substitute completely or at least partially the expensive gas SF6. This aspect is also important with respect to environmental considerations (greenhouse effect). As an alternative, CO2/SF6 mixtures are chosen. Prebreakdown phenomena were investigated for 1,33 MHz of VFT, positive polarity, non-uniform field distribution with admixtures of SF6 to CO2 of 10 %, 20 %, 30 %, 40 % and a pressure range from 0,1 to 0,8 MPa.
Keywords :
SF6 insulation; electric breakdown; electric connectors; environmental management; insulator testing; power system transients; busduct connector; electrical energy transport; environmental considerations; fast transients; gas insulated line; nonuniform field distribution; positive polarity; prebreakdown phenomena; Breakdown voltage; Cathodes; Electric breakdown; Electrodes; Gas insulated transmission lines; Gas insulation; Image intensifiers; Needles; Sulfur hexafluoride; Testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Gas Discharges and Their Applications, 2008. GD 2008. 17th International Conference on
Conference_Location :
Cardiff
Print_ISBN :
978-0-9558052-0-2
Type :
conf
Filename :
5379380
Link To Document :
بازگشت