DocumentCode :
512860
Title :
Transient stability analysis of Gadong Power Station
Author :
Salam, M.A. ; Morsidi, Hj ; Ottman, Nadia
Author_Institution :
Dept. of Electr. & Commun. Eng., Inst. Technol. Brunei, Brunei
fYear :
2009
fDate :
10-12 Nov. 2009
Firstpage :
1
Lastpage :
3
Abstract :
Transient stability analysis is very important to find the behavior of the synchronous machines under faulted condition. In this paper, IPSA simulation software is used to study the transient stability analysis of Gadong power station. Three-phase faults are considered at the busbar 1415LPS and 2829GPS1 with different fault clearing times. From the location at 1415LPS busbar, it is found that the generators of the Gadong I power station are stable for the fault clearing times of 0.1 s and 0.3 s and becomes unstable for the fault clearing time of 0.6 s and 0.7 s. At the other location of the busbar 2829GPS1, the generators of the Gadong I power station becomes unstable for the fault clearing time 0.7 s.
Keywords :
busbars; power stations; power system faults; power system transient stability; synchronous machines; 1415LPS busbar; 2829GPS1 busbar; Gadong I power station; IPSA simulation software; faulted condition; synchronous machines; three phase faults; transient stability analysis; Circuit faults; Power generation; Power system analysis computing; Power system faults; Power system planning; Power system stability; Power system transients; Propagation losses; Stability analysis; Transient analysis;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electric Power and Energy Conversion Systems, 2009. EPECS '09. International Conference on
Conference_Location :
Sharjah
Print_ISBN :
978-1-4244-5477-8
Type :
conf
Filename :
5415700
Link To Document :
بازگشت