• DocumentCode
    519138
  • Title

    Lightning performance of covered conductors overhead distribution lines

  • Author

    Thanasaksiri, T.

  • Author_Institution
    Dept. of Electr. Eng., ChiangMai Univ., Chiang Mai, Thailand
  • fYear
    2010
  • fDate
    19-21 May 2010
  • Firstpage
    284
  • Lastpage
    288
  • Abstract
    This paper analyzes the lightning performance of 22 kV, ChiangMai substation 4 to Doi-Suthep, overhead distribution line with covered conductors. The performance of line which related to the insulator flashover has been modeled and analyzed using EMTP. The backflashover rate (BFOR), shielding failure flashover rate (SFFOR) and induced voltage flashover rate (IVFOR) of line have been determined. The number of lightning flashovers from simulation, by applying ground flash density Ng = 6.5 × 10-5 Td2.277, are close with the data from the line outages recorder.
  • Keywords
    flashover; overhead line conductors; power overhead lines; shielding; ChiangMai substation; backflashover rate; covered conductors overhead distribution lines; ground flash density; induced voltage flashover rate; insulator flashover; lightning performance; line outages recorder; shielding failure flashover rate; Cable insulation; Conducting materials; Conductors; Flashover; Lightning; Power cable insulation; Power cables; Power distribution lines; Substations; Wire;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Engineering/Electronics Computer Telecommunications and Information Technology (ECTI-CON), 2010 International Conference on
  • Conference_Location
    Chaing Mai
  • Print_ISBN
    978-1-4244-5606-2
  • Electronic_ISBN
    978-1-4244-5607-9
  • Type

    conf

  • Filename
    5491486