DocumentCode
519172
Title
Analysis of insulating oil to evaluate the condition of power transformer
Author
Phadungthin, Rattanakorn ; Chaidee, Ekkachai ; Haema, Juthathip ; Suwanasri, Thanapong
Author_Institution
German Grad. Sch. of Eng., King Mongkut´´s Univ. of Technol., Bangkok, Thailand
fYear
2010
fDate
19-21 May 2010
Firstpage
108
Lastpage
111
Abstract
The condition evaluation of insulating oil of power transformer is performed by oil contamination test and the dissolved gas analysis method. The first technique comprises of dielectric strength, interfacial tension, acidity, water content, color, and power factor. The limit value is assigned to each diagnostic test result in order to classify the condition of insulating oil as good, suspect, and poor. The second technique is based on the key gases and the Duval triangle to distinguish the possible fault types by analyzing the amount of gases dissolved in the insulating oil. Two transformer models rated 115/22 kV, 25 MVA and 230/69/22 kV, 200 MVA are selected in the analysis because of their available historical test data. The problems such as overheated cellulose, corona in oil, and thermal fault are finally recognized.
Keywords
power transformer insulation; transformer oil; Duval triangle; apparent power 25 MVA; diagnostic test; dielectric strength; dissolved gas analysis method; insulating oil analysis; oil contamination test; power factor; power transformer; voltage 115 kV; voltage 22 kV; Dielectrics and electrical insulation; Dissolved gas analysis; Gas insulation; Gases; Oil insulation; Performance evaluation; Petroleum; Power transformer insulation; Power transformers; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Engineering/Electronics Computer Telecommunications and Information Technology (ECTI-CON), 2010 International Conference on
Conference_Location
Chaing Mai
Print_ISBN
978-1-4244-5606-2
Electronic_ISBN
978-1-4244-5607-9
Type
conf
Filename
5491521