• DocumentCode
    523301
  • Title

    Dynamic line rating protection for wind farms overview of project

  • Author

    Aten, Martin ; Ferris, Robert

  • Author_Institution
    E.ON Engineering
  • fYear
    2009
  • fDate
    3-4 Nov. 2009
  • Firstpage
    1
  • Lastpage
    29
  • Abstract
    A Dynamic Line Rating (DLR) protection relay has been developed which calculates the line rating based on weather conditions. It is applied to Central Networks´ Skegness to Boston 132kV line and co-ordinates with their control system in case the latter fails. DLR is a cost effective alternative to re-inforcing the overhead lines where there is a constraint to the DG connection due to the fixed line ratings. Analysis of the site data shows a close co-ordination between the actual and the theoretical calculations of the conductor temperature. The conservative assumptions made about wind direction and solar radiation are also shown to provide a good safety margin.
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Substation Technology 2009: Analysing the Strategic and Practical Issues of Modern Substation, IET Conference on
  • Conference_Location
    Birmingham, UK
  • Type

    conf

  • Filename
    5521889