DocumentCode :
52557
Title :
Analysis of Transient Performance of Grounding System Considering Soil Ionization by Time Domain Method
Author :
Bo Zhang ; Jinpeng Wu ; Jinliang He ; Rong Zeng
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Volume :
49
Issue :
5
fYear :
2013
fDate :
May-13
Firstpage :
1837
Lastpage :
1840
Abstract :
The grounding system is very important for lightning protection. If the lightning current is large enough, soil will be ionized, which will have a great effect on the transient performance of the grounding system. In this paper, an efficient time domain method is proposed to analyze the transient performance of the grounding system. The method takes account of nonlinear soil ionization, the shielding effect among electrodes, and frequency-dependent parameters all together. First, a frequency domain circuit model is set up based on a moment method coupling with circuit theory. Then, the model is approximated by a frequency-independent circuit model with the help of vector fitting method. Finally, the time-varying soil ionization is considered by making corresponding parameters time-varying when a time domain method is used to solve the circuit model. The method is validated by field test.
Keywords :
earthing; frequency-domain analysis; ionisation; lightning protection; time-domain analysis; time-varying networks; electrodes; frequency-dependent parameters; frequency-independent circuit model; grounding system; lightning current; lightning protection; time domain method; time-varying soil ionization; transient performance analysis; vector fitting method; Grounding; ionization; lightning; time domain analysis;
fLanguage :
English
Journal_Title :
Magnetics, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9464
Type :
jour
DOI :
10.1109/TMAG.2013.2243824
Filename :
6514729
Link To Document :
بازگشت