  • Abstract
    In February and December 2012, SaskPower experienced two flashovers of "clean" Fiberglass-Reinforced Plastic (FRP) hot stick during cold weather live-line work under steady-state 230 kV ac system conditions. As for SaskPower, Manitoba Hydro had two separate live-line tool flashover events, in 1997 and 2002. Clean-fog tests and non-uniform wetting tests at Hydro-Quebec Research Institute (IREQ), and cold-fog tests at Kinectrics and UQAC were carried out to explain these flashovers. The laboratory tests demonstrated that inadvertent contamination of clean tools at a very light level () of Equivalent Salt Deposit Density (ESDD) likely reduced voltage withstand capability of FRP hot sticks, particularly under freezing conditions. The flashover mechanism was identified when surfaces become fully wetted by the environment or surrounding fog. However, the source of moisture in field flashovers well below 0°C, i.e. as low as -19°C, was not identified. This study is based on laboratory tests and on using available pollution flashover models to explain the results. In this paper, the main objective is to determine the potential and electric field distribution along a FRP hot stick under dry condition and non-uniform wetting. A commercial software, COMSOL MultiphysicsTM, based on the finite element method (FEM), was used for the three-dimensional modeling and simulations. The results obtained will be useful to improve knowledge on the determination of discharge initiation conditions based on electric field distributions along a FRP hot stick.
  • Keywords
    electric fields; finite element analysis; flashover; power overhead lines; COMSOL Multiphysics; EHV live-line work; FRP hot stick; ac system conditions; cold weather live-line work; discharge initiation condition determination; dry condition; electric field distribution; fiberglass-reinforced plastic hot stick; finite element method; non-uniform wetting; pollution flashover models; three-dimensional FEM electrical field calculation; Accidents; Conductors; Electric fields; Electrodes; Finite element analysis; Flashover; Surface contamination; Electrical field calculation; FRP hot stick; flashover; freezing condition.; live-line work;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2014.004580
  • Filename
    7031502