• DocumentCode
    535600
  • Title

    Wavelet based islanding detection of DC-AC inverter interfaced DG systems

  • Author

    Hanif, M. ; Dwivedi, U.D. ; Basu, M. ; Gaughan, K.

  • Author_Institution
    Dept. of Electr. Eng. Syst., Dublin Inst. of Technol., Dublin, Ireland
  • fYear
    2010
  • fDate
    Aug. 31 2010-Sept. 3 2010
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    The increased penetration of distributed generation (DG) often connected to grid through dc-ac interface has made islanding detection an important and challenging issue to power engineers. Several methods based on passive and active detection scheme have been proposed in the literature. While passive schemes have a large non detection zone (NDZ), concern has been raised on active method due to its degrading power quality effect. This paper proposes a wavelet based passive islanding detection scheme with almost zero NDZ for dc-ac inverter interfaced grid connected DGs. The key idea is to utilize the spectral changes in the higher frequency components of PCC voltage occurring after islanding condition. The effectiveness of the proposed method is tested through case studies on a photovoltaic DG system.
  • Keywords
    DC-AC power convertors; distributed power generation; photovoltaic power systems; power grids; power system interconnection; wavelet transforms; DC-AC inverter; NDZ; PCC voltage; connected grid; distributed generation; non detection zone; photovoltaic DG system; wavelet based islanding detection; Discrete wavelet transforms; Filter bank; Inverters; Wavelet analysis; Wavelet coefficients; Distributed generation; islanding detection; non detection zone; wavelet transform;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Universities Power Engineering Conference (UPEC), 2010 45th International
  • Conference_Location
    Cardiff, Wales
  • Print_ISBN
    978-1-4244-7667-1
  • Type

    conf

  • Filename
    5649202