Over-reaching factor for distance relay with quadrilateral characteristic for inter phase faults
Author
Shateri, H. ; Jamali, S.
Author_Institution
Centre of Excellence for Power Syst. Autom. & Oper., Iran Univ. of Sci. & Technol., Tehran, Iran
fYear
2010
fDate
Aug. 31 2010-Sept. 3 2010
Firstpage
1
Lastpage
6
Abstract
Fault resistance is a source of error for distance relays leading to deviation of the measured impedance from its actual value. The presence of the fault resistance not only leads to measured resistance deviation, but also affects the measured reactance. This would lead to either under-reaching or over-reaching. This paper investigates the over-reaching aspect by defining over-reaching factor for quadrilateral distance characteristic in the case of inter phase, phase to phase and three phase, faults. In addition, variation of this factor due to changes in the power system conditions is investigated.
Keywords
electric impedance measurement; power system faults; relay protection; distance relay; fault resistance; impedance measurement; inter phase fault; over reaching factor; quadrilateral characteristic; Circuit faults; Earth; Electrical resistance measurement; Impedance; Impedance measurement; Protective relaying; Resistance; Distance relay; Fault resistance; Measured impedance; Over-reaching factor; Quadrilateral characteristic;