DocumentCode
538602
Title
Analysis of STATCOM under 3 phase balanced reactive load
Author
Balikci, Abdül ; Akpinar, Eyüp
Author_Institution
Elektrik-Elektron. Muhendisligi, Dokuz Eylul Univ., Izmir, Turkey
fYear
2010
fDate
2-5 Dec. 2010
Firstpage
137
Lastpage
141
Abstract
7 level cascaded voltage source inverter structure is presented as Static Synchronous Compensator (STATCOM). Selective harmonic elimination method, synchronous reference frame instantaneous reactive power theory method is applied. DC link capacitors voltage control algorithm is also used. Performance of STATCOM is examined in instantaneous load change from capacitive to inductive and vice versa. Rapid prototyping is applied for STATCOM. Matlab simulation and Matlab-DSP coworking simulation results are compared.
Keywords
invertors; reactive power; static VAr compensators; 3 phase balanced reactive load; Matlab-DSP coworking simulation; STATCOM analysis; cascaded voltage source inverter structure; selective harmonic elimination method; static synchronous compensator; synchronous reference frame instantaneous reactive power theory; Automatic voltage control; Converters; Digital signal processing; Harmonic analysis; Inverters; Power system harmonics; Reactive power;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical, Electronics and Computer Engineering (ELECO), 2010 National Conference on
Conference_Location
Bursa
Print_ISBN
978-1-4244-9588-7
Electronic_ISBN
978-605-01-0013-6
Type
conf
Filename
5698214
Link To Document