• DocumentCode
    539041
  • Title

    The use of arc-suppression coils in power systems with open-delta regulators

  • Author

    Burgess, R. ; Ahfock, A.

  • Author_Institution
    Univ. of Southern Queensland, Toowoomba, QLD, Australia
  • fYear
    2010
  • fDate
    5-8 Dec. 2010
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Arc-suppression coil systems are able to improve high voltage system reliability and safety. If these systems are used in high voltage power distribution networks which incorporate open-delta regulators, dangerous over-voltages can occur. Because the open-delta regulators increase the line to earth voltage in two phases only, out of balance line to earth capacitance currents flow through the arc-suppression coil. It is shown that under certain conditions the resultant system voltages can reach dangerous levels. It is recommended that a detailed analysis be carried out before arc-suppression coils and open-delta regulators are installed in the same power system.
  • Keywords
    coils; power distribution reliability; voltage regulators; arc-suppression coils; currents flow; earth capacitance; high voltage power distribution networks; high voltage system reliability; open-delta regulators; power systems; Capacitance; Coils; Earth; Grounding; Inductors; Regulators; Voltage control; Petersen coil; arc-suppression; open-delta; symmetrical components;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Universities Power Engineering Conference (AUPEC), 2010 20th Australasian
  • Conference_Location
    Christchurch
  • Print_ISBN
    978-1-4244-8379-2
  • Electronic_ISBN
    978-1-4244-8380-8
  • Type

    conf

  • Filename
    5710799