Title :
PDC patterns of biodegradable transformers insulation oil after experienced faults and at different moisture levels
Author :
Muhamad, N.A. ; Phung, B.T. ; Blackburn, T.R.
Author_Institution :
Fac. of Electr. Eng., Univ. Teknol. Malaysia, Skudai, Malaysia
Abstract :
The PDC method is a simple and reliable analysis tool to monitor transformer insulation systems. Based on PDC measurements of the biodegradable oil in a healthy oil condition at different moisture levels and after faults (Partial discharge, Overheating and Arcing) fault identification can be achieved by comparing the PDC pattern of an oil sample against the PDC fingerprints. Furthermore, the relationship curves between the oil moisture level toward its conductivity level and measured capacitance value have been established. These curves can be used to predict the oil moisture condition and the fault type.
Keywords :
fault location; partial discharge measurement; transformer oil; PDC patterns; biodegradable transformers insulation oil; experienced faults; fault identification; oil moisture level; Circuit faults; Conductivity; Current measurement; Insulation; Moisture; Partial discharges; Petroleum; acrhing; biodegradable oil; depolarization current; mositure; overheting; partial discharge; polarization current;
Conference_Titel :
Universities Power Engineering Conference (AUPEC), 2010 20th Australasian
Conference_Location :
Christchurch
Print_ISBN :
978-1-4244-8379-2
Electronic_ISBN :
978-1-4244-8380-8