DocumentCode
541193
Title
Energy based contact burning diagnosis and Research of on-load tap changers
Author
Wang, Chunning ; Chen, Wei ; Chen, Lin ; Ma, Hongzhong ; Gao, Peng ; Wang, Chunliang
Author_Institution
Nanjing Power Supply Co., Jiangsu Electr. Power Co., Nanjing, China
fYear
2010
fDate
13-16 Sept. 2010
Firstpage
1
Lastpage
5
Abstract
Contact burning is one of the main faults of transformer on-load tap changers (OLTC). If contact burning fault diagnosis is not timely, the decreasing contact area, increasing contact resistance and the increasing arc and heat during the witching processes will cause further burning. Researches on contact burning failure were done and a feature analysis method based on wavelet packet energy entropy of OLTC was proposed in this paper. After the comparison of the time domain vibration signal energy in the normal and fault conditions, the wavelet packet energy entropy was taken advantage to analysis the contact burning fault. Fault symptoms of OLTC were extracted by the simplified wavelet packet energy entropy. The contact burning fault can be determined by the symptoms and the results of the experiment show that this approach was feasible for the condition monitoring of OLTC.
Keywords
fault diagnosis; power transformers; contact burning failure; contact resistance; energy based contact burning diagnosis; fault diagnosis; feature analysis method; on-load tap changers; time domain vibration signal energy; transformer; wavelet packet energy entropy; witching processes; Entropy; Heating; Monitoring; Switches; Vibrations; Wavelet packets; On-load tap changer; contact burning; energy method; feature extraction;
fLanguage
English
Publisher
ieee
Conference_Titel
Electricity Distribution (CICED), 2010 China International Conference on
Conference_Location
Nanjing
Print_ISBN
978-1-4577-0066-8
Type
conf
Filename
5735893
Link To Document