• DocumentCode
    541200
  • Title

    The improvement and analysis of anti-mistake device of switchgear cabinet

  • Author

    Mei Zhengnan ; Zhang Yingqi ; Zhang Youyun

  • Author_Institution
    Chuzhou Power Supply Co., Chuzhou, China
  • fYear
    2010
  • fDate
    13-16 Sept. 2010
  • Firstpage
    1
  • Lastpage
    7
  • Abstract
    The 10~35kV switchgear cabinet, in the current production and power system running, has been installed with the isolation baffle plate that can shield electrical part, but has not been designed to be installed with closed lock device that prevent the baffle plate opening during the checking and repairing. Therefore, the existing security measure completely depend on the personnel´s security consciousness and supervision and the accident has happened. In this article, we analyze the current design disfigurement of switchgear cabinet, and hereby introduce a closed lock device that can reliably close the isolation baffle plate to prevent people incorrectly opening to touch electrical part. It not only make up the design disfigurement of anti-mistake of switchgear cabinet without changing the run operation process and affecting the, but also add the device of enforcement for the safety rule be profitable to anti-mistake, add protection for personnel safety.
  • Keywords
    electric shocks; safety; safety devices; switchgear; antimistake device; closed lock device; isolation baffle plate; personnel safety; personnel security consciousness; power system; switchgear cabinet; voltage 10 kV to 35 kV; Axles; Catalogs; Switches; Welding; Wheels; HV equipment; anti-mistake safety device; switchgear cabinet;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electricity Distribution (CICED), 2010 China International Conference on
  • Conference_Location
    Nanjing
  • Print_ISBN
    978-1-4577-0066-8
  • Type

    conf

  • Filename