    Ferro-resonance over-voltage and power frequency over-voltage on the neutrals of 220kV power transformer and corresponding protection strategy

  • Author

    Yu Hua-peng ; Chen Shui-ming ; Hong-qiao, Yu ; Yang Peng-cheng ; Yin Hua ; Wu Gaolin

  • Author_Institution
    Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
  • fYear
    2010
  • fDate
    13-16 Sept. 2010
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    In order to limit short-circuit current and satisfy the need of relay setting, only part of the 220kV power transformer is grounded, so on the neutrals of ungrounded transformers will appear the over-voltage. Currently the value of over-voltage on transformer neutral point and the corresponding protection strategy is based on theoretical formula, this article use the PSCAD/EMTDC software to calculate the over-voltage on the neutral point of 4 ungrounded power transformers in Chongqing 220kV power grid, the result shows that the power frequency transient over-voltage on the neutrals may reach 178kV, If the single-phase grounding fault occurs in ungrounded power system, the power frequency over-voltage on the neutrals will be more serious and rise to 138.6kV. Non-full phase operation may cause serious ferro-resonance over-voltage on the neutrals of no-load transformer, which may last for seconds and may rise to 723.7kV, causing serious threat to the transformer neutrals and line-side equipment. The article also studies the gap parameter which should be taken on the neutrals of 220kV transformers at the end.
  • Keywords
    earthing; overvoltage protection; power transformers; short-circuit currents; Chongqing power grid; PSCAD-EMTDC software; ferroresonance overvoltage; no-load transformer; power frequency transient overvoltage; power transformer; protection strategy; relay setting; short-circuit current; single-phase grounding fault; transformer neutral point; ungrounded power transformers; voltage 220 kV; Circuit faults; Grounding; Power transformer insulation; Substations; Transient analysis; arrester; gap; lightning over-voltage; neutral point; power frequency over-voltage; power transformer;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electricity Distribution (CICED), 2010 China International Conference on
  • Conference_Location
    Nanjing
  • Print_ISBN
    978-1-4577-0066-8
  • Type

    conf

  • Filename
    5736099