    Harmonic suppression and reactive control of NQ station in Genan HVDC system

  • Author

    Yang Guang-Liang ; Tai Neng-Ling ; Wang Yong

  • Author_Institution
    Dept. of Electr. Eng., Shanghai Jiao Tong Univ., Shanghai, China
  • fYear
    2010
  • fDate
    13-16 Sept. 2010
  • Firstpage
    1
  • Lastpage
    8
  • Abstract
    This article has analyzed the origin and the harm of harmonics in the HVDC system. The harmonics analysis has been done to the DC and AC side of NQ substation in Ge-Nan HVDC system. And found the order 13 harmonic filters capacities are insufficient, so DA32 capacitor group will be transformed into HP11.8 filter. The reactive power control method of NQ station is also introduced in this paper, especially Umax, Q-control and Qmax control algorithms. The tests validated the AC filter switching sequence. The reason of F1 group filters must be devoted firstly before the HVDC system starts is analyzed.
  • Keywords
    HVDC power convertors; harmonic analysis; power harmonic filters; reactive power control; substations; AC filter switching; Fl group filter; Genan HVDC System; NQ substation; Q-control; Qmax control; harmonic filter; harmonic suppression; harmonics analysis; reactive power control method; HVDC transmission; Harmonic analysis; Position measurement; Power harmonic filters; Switches; AC filter; HVDC; RPC; harmonics; switching;