• DocumentCode
    541401
  • Title

    The new real-time control system of reactive power optimization

  • Author

    Duan, Xinhui ; Zhou, Yilin ; Liu, Junyong ; Yang, Liu

  • Author_Institution
    Production Technol. Dept., Guangdong Power Grid Corp., Guangzhou, China
  • fYear
    2010
  • fDate
    13-16 Sept. 2010
  • Firstpage
    1
  • Lastpage
    12
  • Abstract
    This paper uses non-linear programming optimal power flow algorithm with slack constraint to analyze reactive power real-time optimization problems in actual grid. And considering the effect of control action sequence on the optimal control effect, the control strategies of the reactive power real-time optimization control system are improved. The control action sequences in normal and failure circumstance are separately determined based on the control variables´ active power loss control sensibility and voltage control sensibility, effectively avoiding the system oscillation caused by control variables changing at the same time. The application on IEEE-30 bus system verifies effectiveness and practicality of the algorithm and control strategy in this paper.
  • Keywords
    load flow control; nonlinear programming; optimal control; power grids; reactive power control; voltage control; active power loss control sensibility; nonlinear programming optimal power flow algorithm; optimal control; power grid; reactive power optimization; real-time control system; voltage control sensibility; Analytical models; Biological system modeling; Cities and towns; Fluid flow measurement; Optimization; Voltage control; Voltage measurement; constraints slacking; control action sequence; control sensitivity; optimal power flow; reactive power optimization;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electricity Distribution (CICED), 2010 China International Conference on
  • Conference_Location
    Nanjing
  • Print_ISBN
    978-1-4577-0066-8
  • Type

    conf

  • Filename
    5736115