• DocumentCode
    54251
  • Title

    Three-Dimensional FDTD Calculation of Lightning-Induced Voltages on a Multiphase Distribution Line With the Lightning Arresters and an Overhead Shielding Wire

  • Author

    Tatematsu, Akiyoshi ; Noda, Toshio

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Yokosuka, Japan
  • Volume
    56
  • Issue
    1
  • fYear
    2014
  • fDate
    Feb. 2014
  • Firstpage
    159
  • Lastpage
    167
  • Abstract
    To suppress the lightning-induced voltages on a distribution line, lightning arresters and/or overhead shielding wire can be installed, and the effectiveness of these countermeasures are usually studied by simulations. Traditionally, field-to-transmission line coupling techniques based on the distributed-parameter circuit theory are used for the calculation of the lightning-induced voltages. Recently, the finite-difference time-domain (FDTD) method that directly and numerically solves Maxwell´s equations was applied to the calculation of the lightning-induced voltages. Compared with the conventional methods, the FDTD-based calculation is advantageous in terms of the modeling of inhomogeneous ground parameters, 3-D structures, and grounding systems. But, in the previous works, the distribution line was simulated simply by a single-phase line. Moreover, the representation of lightning arresters in the FDTD method was not yet established. This paper proposes a technique to incorporate the lightning arresters in the FDTD-based lightning overvoltage calculations. In this technique, the voltage-current relationships of the lightning arresters are represented by piecewise linear curves, which can be obtained directly from the data sheets or measured results. For validation purpose, the lightning-induced voltages on a three-phase distribution line equipped with the lightning arresters and a multipoint-grounded overhead shielding wire are calculated by the proposed method, and the results are compared with those obtained by the conventional method and a very good agreement is found.
  • Keywords
    arresters; earthing; finite difference time-domain analysis; lightning protection; power distribution protection; Maxwell equations; distributed parameter circuit theory; finite difference time-domain method; grounding systems; lightning arresters; lightning induced voltage; lightning overvoltage calculation; multiphase distribution line; overhead shielding wire; piecewise linear curve; three dimensional FDTD calculation; voltage-current relationships; Arresters; Finite difference methods; Lightning; Mathematical model; Resistors; Time-domain analysis; Wires; Finite-difference time-domain (FDTD) method; lightning protection; lightning-induced voltages; power distribution lines;
  • fLanguage
    English
  • Journal_Title
    Electromagnetic Compatibility, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9375
  • Type

    jour

  • DOI
    10.1109/TEMC.2013.2272652
  • Filename
    6566033