Abstract
Ferroresonance overvoltage is an unwanted electrical phenomenon, which may cause over voltages and over currents in the electrical power. This paper studies the effect of circuit breaker shunt resistance, and Metal Oxide Surge Arrester (MOSA) on the control of chaotic ferroresonance in a Potential transformer (PT). It is expected that this resistance, and MOSA generally can cause ferroresonance ‘dropout’. For confirmation this phenomenon, simulation is investigated on a one phase potential transformer rated 100VA, 275kV. Simulation results reveal that considering shunt resistance on the circuit breaker and MOSA in parallel with potential transformer exhibits a great mitigating effect of ferroresonance over voltages. Significant effect on the onset of ferroresonance, the range of parameter values that may cause to chaotic ferroresonance is obtained and presented.
Keywords
Chaos; Circuit breakers; Ferroresonance; Integrated circuit modeling; Resistance; Voltage control; Voltage transformers; Bifurcation diagram; Chaos; Circuit breakers Shunt Resistance; Ferroresonance oscillations; MOSAv; Potential Transformers;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Engineering (ICEE), 2011 19th Iranian Conference on
Conference_Location
Tehran, Iran
Print_ISBN
978-1-4577-0730-8
Electronic_ISBN
978-964-463-428-4
Type
conf
Filename
5955527
Link To Document