Analysis of differential protection response for cross-country faults in transmission lines
Author :
Solak, Krzysztof ; Rebizant, Waldemar
Author_Institution :
Inst. of Electr. Power Eng., Wroclaw Univ. of Wroclaw, Wroclaw, Poland
fYear :
2010
fDate :
20-22 Sept. 2010
Firstpage :
1
Lastpage :
4
Abstract :
This paper studies impact of cross-country faults in double-circuit lines on current differential relay. The protection in case of double-circuit lines should trip faults only in protected zone and not overreact for outside disturbances. The problem is when cross-country faults occur, which means that fault is incepted in the protected zone and also outside at the same time or after short break. For such a situation the differential protection may trip external faults incorrectly or may not trip internal faults. This situation should be analyzed and suggestions for protection improvement proposed. Signals for tests originated from ATP-EMTP simulations.
Keywords :
EMTP; power transmission faults; power transmission lines; power transmission protection; ATP-EMTP simulations; cross-country faults; current differential relay; differential protection response analysis; double-circuit lines; external faults; internal faults; transmission lines; Circuit faults; Fault currents; Mathematical model; Power transmission lines; Relays; Resistance; Trajectory; ATP-EMTP simulation; cross-country fault; current differential protection; double-circuit transmission line;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Modern Electric Power Systems (MEPS), 2010 Proceedings of the International Symposium
Conference_Location :
Wroclaw
Print_ISBN :
978-83-921315-7-1
Type :
conf
Filename :
6007268
Link To Document :
بازگشت