DocumentCode
55943
Title
Partial discharge analysis of gas insulated systems at high voltage AC and DC
Author
Piccin, Roland ; Mor, Armando ; Morshuis, Peter ; Girodet, Alain ; Smit, Johan
Author_Institution
Delft Univ. of Technol., Delft, Netherlands
Volume
22
Issue
1
fYear
2015
fDate
Feb. 2015
Firstpage
218
Lastpage
228
Abstract
Partial discharge (PD) measurements are commonly used for monitoring and diagnostics of AC gas insulated systems (GIS). Because of the growing importance of DC GIS, a research project was started focused on the measurement and interpretation of PD signals obtained under DC stress. Results are presented using IEC60270 and unconventional methods through UHF antenna and high frequency current transformer (HFCT) on three different PD generating defects in a GIS chamber. The results of the PD analysis of the defects are compared for AC and DC stress. Phase resolved partial discharge patterns (PRPD) are used for the HVAC analysis, whereas time resolved partial discharge patterns (TRPD) are used for HVDC analysis. Finally, relevant characteristics of PD patterns in HVAC and HVDC are presented and related with the physical phenomena of the discharges.
Keywords
UHF antennas; current transformers; gas insulated substations; partial discharge measurement; AC GIS; AC gas insulated systems; DC GIS; DC stress; GIS chamber; IEC60270 methods; UHF antenna; high frequency current transformer; high voltage AC; high voltage DC; partial discharge analysis; partial discharge measurements; phase resolved partial discharge patterns; time resolved partial discharge patterns; Corona; Discharges (electric); HVDC transmission; Needles; Partial discharges; Sulfur hexafluoride; HVDC GIS; SF6; corona discharge; gas insulated substations; high voltage; partial discharges;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
1070-9878
Type
jour
DOI
10.1109/TDEI.2014.004711
Filename
7033390
Link To Document