DocumentCode :
56090
Title :
High Altitude Effect on Corona Inception Voltages of DC Power Transmission Conductors Based on the Mobile Corona Cage
Author :
Xingming Bian ; Liming Wang ; Yunpeng Liu ; Yingjian Yang ; Zhicheng Guan
Author_Institution :
Grad. Sch. at Shenzhen, Tsinghua Univ., Shenzhen, China
Volume :
28
Issue :
3
fYear :
2013
fDate :
Jul-13
Firstpage :
1971
Lastpage :
1973
Abstract :
In order to investigate the high altitude effect on dc corona inception voltage of power transmission lines, a mobile corona cage test system was constructed. The experiments were carried in Wuhan, Xining, Geermu, and Nachitai, respectively. Photons released as a result of corona discharge on the conductors were detected by the ultraviolet image detector. Both positive and negative corona inception voltages could be acquired by the “tangent method” based on the measured data. The approximate linear altitude correction formulas were suggested.
Keywords :
conductors (electric); corona; power transmission lines; ultraviolet detectors; China; DC power transmission conductors; corona discharge; dc corona inception voltage; high altitude effect; linear altitude correction; mobile corona cage test system; power transmission lines; tangent method; ultraviolet image detector; Conductors; Corona; Detectors; Discharges (electric); Photonics; Power transmission lines; Voltage measurement; Altitude; corona cage; corona discharge; corona inception voltage; negative; positive; ultraviolet;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2013.2258818