DocumentCode :
569894
Title :
Investigation of thermal and mechanical stresses of arcing contacts in circuit breakers
Author :
Fnineche, C. ; Aitken, O.
Author_Institution :
High Voltage Switchgear Res. Center (ARC), Alstom Grid, Villeurbanne, France
fYear :
2012
fDate :
14-17 May 2012
Firstpage :
386
Lastpage :
389
Abstract :
The tulip contact is one of the elements which constitute arcing contacts in a circuit breaker. This element plays an important role in breaking of fault currents (short circuit currents). Loss of contact force or/and opening of contact fingers can happen during short circuit test if certain parameters are not considered in the design of the tulip. In this article, we analyse thermal and mechanical parameters which influence the quality of arcing. Results of experiments and calculations have been compared and recommendations are made to improve arcing contact design.
Keywords :
circuit breakers; electrical contacts; short-circuit currents; stress analysis; thermal stresses; arcing contact design; circuit breakers; fault currents; mechanical parameters analysis; mechanical stresses investigation; short circuit currents; thermal parameters analysis; thermal stresses investigation; tulip contact; arcing contacts; circuit breaker; electrical stress; mechanical stress; thermal stress; tulip;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electrical Contacts (ICEC 2012), 26th International Conference on
Conference_Location :
Beijing
Electronic_ISBN :
978-1-84919-508-9
Type :
conf
DOI :
10.1049/cp.2012.0680
Filename :
6301925
Link To Document :
بازگشت