DocumentCode
569894
Title
Investigation of thermal and mechanical stresses of arcing contacts in circuit breakers
Author
Fnineche, C. ; Aitken, O.
Author_Institution
High Voltage Switchgear Res. Center (ARC), Alstom Grid, Villeurbanne, France
fYear
2012
fDate
14-17 May 2012
Firstpage
386
Lastpage
389
Abstract
The tulip contact is one of the elements which constitute arcing contacts in a circuit breaker. This element plays an important role in breaking of fault currents (short circuit currents). Loss of contact force or/and opening of contact fingers can happen during short circuit test if certain parameters are not considered in the design of the tulip. In this article, we analyse thermal and mechanical parameters which influence the quality of arcing. Results of experiments and calculations have been compared and recommendations are made to improve arcing contact design.
Keywords
circuit breakers; electrical contacts; short-circuit currents; stress analysis; thermal stresses; arcing contact design; circuit breakers; fault currents; mechanical parameters analysis; mechanical stresses investigation; short circuit currents; thermal parameters analysis; thermal stresses investigation; tulip contact; arcing contacts; circuit breaker; electrical stress; mechanical stress; thermal stress; tulip;
fLanguage
English
Publisher
iet
Conference_Titel
Electrical Contacts (ICEC 2012), 26th International Conference on
Conference_Location
Beijing
Electronic_ISBN
978-1-84919-508-9
Type
conf
DOI
10.1049/cp.2012.0680
Filename
6301925
Link To Document