DocumentCode :
570399
Title :
Fault identification method based on current fault limiter resonant voltage difference signal
Author :
Huaxin, Wang ; Yongxi, Zhao
Author_Institution :
ShangHai Univ. of Electr. Power, Shanghai, China
fYear :
2012
fDate :
21-24 May 2012
Firstpage :
1
Lastpage :
4
Abstract :
Series resonant fault current limiter(SRFCL) is practical limiter of EHV. SRFCL control strategy requires resonant capacitor quickly bypassed after fault occurs. Short-circuit fault rapid identification is the key to fast trigger strategy. The paper introduces resonant voltage difference method based on limiter body signal. Simulation model is built to analysis time characteristics from the closing angles and fault distance. Logic protection criterion is designed. A small physical model is built to verify the resonant voltage difference method. Simulation results show that the resonant voltage difference method is not affected by fault parameters, experiments show that it can supply failure criterion signal within 1 ms.
Keywords :
capacitors; fault current limiters; fault diagnosis; power control; power system protection; short-circuit currents; EHV; SRFCL control strategy; fault identification method; logic protection criterion; power control; resonant capacitor; resonant voltage difference signal; series resonant fault current limiter; short-circuit fault; trigger strategy; Capacitors; Circuit faults; Fault diagnosis; Inductors; Integrated circuit modeling; Power systems; Voltage control; Fault Parameters; Fault identification; Resonant Voltage Difference Method; SRFCL;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Innovative Smart Grid Technologies - Asia (ISGT Asia), 2012 IEEE
Conference_Location :
Tianjin
Print_ISBN :
978-1-4673-1221-9
Type :
conf
DOI :
10.1109/ISGT-Asia.2012.6303222
Filename :
6303222
Link To Document :
بازگشت