• DocumentCode
    570399
  • Title

    Fault identification method based on current fault limiter resonant voltage difference signal

  • Author

    Huaxin, Wang ; Yongxi, Zhao

  • Author_Institution
    ShangHai Univ. of Electr. Power, Shanghai, China
  • fYear
    2012
  • fDate
    21-24 May 2012
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Series resonant fault current limiter(SRFCL) is practical limiter of EHV. SRFCL control strategy requires resonant capacitor quickly bypassed after fault occurs. Short-circuit fault rapid identification is the key to fast trigger strategy. The paper introduces resonant voltage difference method based on limiter body signal. Simulation model is built to analysis time characteristics from the closing angles and fault distance. Logic protection criterion is designed. A small physical model is built to verify the resonant voltage difference method. Simulation results show that the resonant voltage difference method is not affected by fault parameters, experiments show that it can supply failure criterion signal within 1 ms.
  • Keywords
    capacitors; fault current limiters; fault diagnosis; power control; power system protection; short-circuit currents; EHV; SRFCL control strategy; fault identification method; logic protection criterion; power control; resonant capacitor; resonant voltage difference signal; series resonant fault current limiter; short-circuit fault; trigger strategy; Capacitors; Circuit faults; Fault diagnosis; Inductors; Integrated circuit modeling; Power systems; Voltage control; Fault Parameters; Fault identification; Resonant Voltage Difference Method; SRFCL;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Innovative Smart Grid Technologies - Asia (ISGT Asia), 2012 IEEE
  • Conference_Location
    Tianjin
  • Print_ISBN
    978-1-4673-1221-9
  • Type

    conf

  • DOI
    10.1109/ISGT-Asia.2012.6303222
  • Filename