• DocumentCode
    57613
  • Title

    Determination of Parameters of Zero-Sequence Equivalent Circuits for Three-Phase Three-Legged YNynd Transformers Based on Onsite Low-Voltage Tests

  • Author

    Ramos, Angel ; Burgos, J. ; Moreno, Alexander ; Sorrentino, Elmer

  • Author_Institution
    Gas Natural Fenosa (Union Fenosa Distribucion), Madrid, Spain
  • Volume
    28
  • Issue
    3
  • fYear
    2013
  • fDate
    Jul-13
  • Firstpage
    1618
  • Lastpage
    1625
  • Abstract
    This paper proposes a new approach for obtaining parameters of the zero-sequence equivalent circuit of three-phase three-legged three-winding YNynd transformers (i.e., transformers with two wye windings and a third delta stabilizing winding). The methodology proposed in this paper includes a complete set of onsite field measurements using commercial equipment (traditionally used for onsite transformer leakage reactance tests). An easy-to-implement determination of the zero-sequence behavior of the YNynd transformer is achieved by means of separating the equivalent T-circuit into two different circuits, one of them to be used when the delta stabilizing winding is closed and the other when this is open. The effect of the resistive component of the zero-sequence impedances is also analyzed and quantified. Onsite measurements on a 45/16.05/10-kV 25-MVA power transformer and their comparison with high-voltage factory tests are presented to demonstrate and validate the proposed methodology.
  • Keywords
    electric impedance measurement; equivalent circuits; power transformer testing; transformer windings; delta stabilizing winding; high-voltage factory tests; onsite field measurements; onsite low-voltage tests; three-phase three-legged YNynd transformers; transformer leakage reactance tests; voltage 10 kV; voltage 16.05 kV; voltage 45 kV; wye windings; zero-sequence equivalent circuits; Circuit faults; Current measurement; Equivalent circuits; Power transformers; Production facilities; Voltage measurement; Windings; Onsite impedance measurements; stabilizing windings; three-winding transformers; transformer zero-sequence equivalent circuit;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2013.2259184
  • Filename
    6515365