DocumentCode :
577325
Title :
Influence of metal deactivator concentration on copper sulfur corrosion in transformer oil
Author :
Huang, Zonghua
Author_Institution :
Beijing Guohua Electr. Power Co., Beijing, China
fYear :
2012
fDate :
17-20 Sept. 2012
Firstpage :
435
Lastpage :
438
Abstract :
Insulating oil plays an important role of insulation in transformers. However, copper sulphide deposition on oil-paper insulation can lead to insulation failures in power transformers. In order to research the corrosive properties after adding dibenzyl disulfide (DBDS) and 2, 6-Di-tert-butyl-4-methylphenol (DBPC), and the ability of inhibiting corrosion after adding metal deactivator in transformer oil, a series of thermal aging tests are carried on a certain brand of Nynas and Karamay oil in this paper. First of all, testing the corrosive sulfur compounds by ASTM D1275B method; And Nynas oil test after adding a certain amount of metal deactivator is made at 90 °C to analyze the changing of dissolved gas-in-oil content is analyzed. Experiments and analysis results show that DBDS instead of DBPC is the corrosive sulfur compounds; Metal deactivation agent can effectively prevent the occurrence of sulfur corrosion, but it consumes rapidly with the thermal aging; the oil dissolved gas content significantly changes after adding metal deactivator in oil. All of the above results can be the foundation for a further study on corrosive sulfur and control measure in transformer oil.
Keywords :
ageing; copper compounds; corrosion; power transformer insulation; transformer oil; 2, 6-Di-tert-butyl-4-methylphenol; ASTM D1275B method; Cu2S; DBDS; DBPC; Karamay oil; Nynas oil; copper sulfur corrosion; copper sulphide deposition; corrosive properties; corrosive sulfur compounds; dibenzyl disulfide; dissolved gas-in-oil content; insulating oil; metal deactivator concentration; oil-paper insulation; power transformers; temperature 90 degC; thermal aging; thermal aging tests; transformer insulation; transformer oil; Aging; Copper; Corrosion; Oil insulation; Power transformer insulation; copper sulfide; corrosion sulfur; dissolved gas; metal deactivator; thermal aging; transformer oil;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
High Voltage Engineering and Application (ICHVE), 2012 International Conference on
Conference_Location :
Shanghai
Print_ISBN :
978-1-4673-4747-1
Type :
conf
DOI :
10.1109/ICHVE.2012.6357143
Filename :
6357143
Link To Document :
بازگشت