Abstract :
In this paper multifractal nature of polarisation (pol) and depolarisation (depol) current of a transformer insulation is identified and shown using a multifractal spectra. Multifractal analysis is carried out on pol and depol current of oil-impregnated pressboard samples of different moisture contents. Multifractal analysis is also carried out for pol and depol current of a transformer before and after oil reclamation. It is shown using multifractal spectra that pol and depol current of transformer insulation are fractal and scales with time. The sandbox method is used in this work to determine multifractal spectrum of pol and depol current for the moment order q = -10 to q = 10, and application of sandbox method to determine multifractal spectrum of pol and depol current is demonstrated.
Keywords :
fractals; polarisation; transformer oil; depol current; depolarisation current; moisture contents; multifractal analysis; multifractal nature; multifractal spectrum; oil-impregnated pressboard; pol current; polarisation current; sandbox method; transformer insulation; Current measurement; Fractals; Moisture; Oil insulation; Power transformer insulation; Voltage measurement; Depolarisation current; Insulation; PDC; Polarisation; Transformer; fractal; multifractal; sandbox method;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Universities Power Engineering Conference (AUPEC), 2012 22nd Australasian
Conference_Location :
Bali
Print_ISBN :
978-1-4673-2933-0
Type :
conf
Filename :
6360247
Link To Document :
بازگشت