Abstract :
This paper deals with the impulse PD (partial discharge) characteristics in oil/pressboard composite insulation systems. We examined the PD starting point in test samples with the oil gap length varied from 1.6 mm to 9.6 mm, which simulated the oil duct in an oil-immersed transformer. Consequently, we found that when the oil gap length was below 4.8 mm, the PD starting point shifted from the oil gap to creepage of a spacer when the oil gap length increased. On the other hand, when the oil gap length was over 4.8 mm, the PD starting point shifted from creepage of a spacer to the oil gap as the oil gap length increased. These results of experiments can be explained by considering the volume effect of the transformer oil and assuming that the fibrous protrusions on the surface of the pressboard had an influence.
Keywords :
partial discharges; transformer oil; PD starting point; fibrous protrusions; impulse PD; oil gap dependence; oil gap length; oil-immersed transformer; oil-pressboard composite insulation system; partial discharge characteristics; partial discharge starting point; spacer creepage; transformer oil; Electric fields; Electrodes; Oil insulation; Partial discharges; Power transformer insulation; Partial Discharge; Pressboard; Transformer oil;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Machines and Systems (ICEMS), 2012 15th International Conference on
Conference_Location :
Sapporo
Print_ISBN :
978-1-4673-2327-7
Type :
conf
Filename :
6401955
Link To Document :
بازگشت