• DocumentCode
    591528
  • Title

    The sag detection strategy for seamless transfer APF-UPS system

  • Author

    Kook-Nam Sung ; Woo-Cheol Lee ; Taeck-Ki Lee

  • Author_Institution
    Dept. of Electr. Eng., HanKyong Nat. Univ., Ansung, South Korea
  • fYear
    2012
  • fDate
    9-12 Oct. 2012
  • Firstpage
    1480
  • Lastpage
    1484
  • Abstract
    In this paper, when voltage sag of the normal grid voltage occurs, detecting the peak voltage for fast mode transfer method is proposed. The conventional detector of sag voltage used in synchronous d-q frame by Digital Phase-Locked-Loop(DPLL). However using this method, the delay time is longer. Despite the sag occurrence of grid voltage, it cannot reflect a sudden change of the grid voltage in the moment of voltage sag, which causes a resulted peak value to be significantly distorted and momentary interruption. Sag detection method is proposed by reducing the delay time caused by these sag. Its effectiveness and capability in instantly detecting are verified via PSIM simulations and experimental results.
  • Keywords
    active filters; delays; digital phase locked loops; power grids; power harmonic filters; power supply quality; uninterruptible power supplies; DPLL; PSIM simulations; delay time reduction; digital phase-locked-loop; fast mode transfer method; momentary interruption; normal grid voltage sag detection strategy; seamless transfer APF-UPS system; synchronous d-q frame; Insulated gate bipolar transistors;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Vehicle Power and Propulsion Conference (VPPC), 2012 IEEE
  • Conference_Location
    Seoul
  • Print_ISBN
    978-1-4673-0953-0
  • Type

    conf

  • DOI
    10.1109/VPPC.2012.6422589
  • Filename
    6422589