Abstract :
This paper presents a new formulation for system state estimation of passive electric distribution networks. The fundamental idea discussed here is how to obtain the state of the system at maximum demand condition using three sources of information: 1) a quasi-symmetric matrix called TRX representing network structure and topology, 2) power measurements at main feeder disconnection devices and reclosers installed in the network, and 3) Energy measurements and estimated load curve of aggregate users at distribution transformers. The method is formulated with real variables for single-phase positive sequence radially operated networks. Results of the application of proposed methodology are presented using the well known IEEE 4-Node test system.
Keywords :
IEEE standards; distribution networks; passive networks; power transformers; state estimation; IEEE 4-node test system; distribution system; distribution transformers; energy measurements; feeder disconnection devices; passive electric distribution networks; quasi-symmetric matrix; single-phase positive sequence; state estimation; Current measurement; Energy measurement; Power measurement; Reactive power; State estimation; Vectors; Voltage measurement; distribution state estimator;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Andean Region International Conference (ANDESCON), 2012 VI
Conference_Location :
Cuenca
Print_ISBN :
978-1-4673-4427-2
Type :
conf
DOI :
10.1109/Andescon.2012.11
Filename :
6424108
Link To Document :
بازگشت