DocumentCode :
601543
Title :
Analysis of delay effects in single-loop controlled grid-connected inverter with LCL filter
Author :
Rui Li ; Bangyin Liu ; Shanxu Duan ; Jinjun Yin ; Xiaolong Jiang
Author_Institution :
State Key Lab. of Adv. Electromagn. Eng. & Technol., Huazhong Univ. of Sci. & Technol., Wuhan, China
fYear :
2013
fDate :
17-21 March 2013
Firstpage :
329
Lastpage :
333
Abstract :
Delay in a grid current single-loop controlled inverter with LCL filter has a great influence on the system stability. The unstable problem of grid-connected inverters with LCL filter is clearly explained from positive feedback concept, and the positive role of delay in system stable control is explored in this paper. Then the range of delay time is calculated to guarantee the system stable. The effects of delay on dynamic and steady state performance of system are also revealed. An optimized delay time is designed to realize stable operation, fast dynamic response and low harmonics of resonance frequency based on the theoretical analysis. Experimental results validate the theoretical analysis about the effects of delay.
Keywords :
delays; feedback; filters; invertors; power grids; LCL filter; delay effects analysis; delay time; fast dynamic response; grid current single-loop controlled inverter; positive feedback; resonance frequency harmonics; single-loop controlled grid-connected inverter; system stable control; theoretical analysis;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Applied Power Electronics Conference and Exposition (APEC), 2013 Twenty-Eighth Annual IEEE
Conference_Location :
Long Beach, CA
ISSN :
1048-2334
Print_ISBN :
978-1-4673-4354-1
Electronic_ISBN :
1048-2334
Type :
conf
DOI :
10.1109/APEC.2013.6520229
Filename :
6520229
Link To Document :