Title :
Transformer failure due to circuit breaker induced switching transients appplicable to the cement industry
Author :
Shipp, David D. ; Dionise, Thomas J. ; Lorch, V.
Abstract :
Switching transients associated with circuit breakers have been observed for many years. Recently this phenomenon has been attributed to a significant number of transformer failures involving primary circuit breaker switching. These transformer failures had common contributing factors such as 1) primary vacuum or SF-6 breaker, 2) short cable or bus connection to transformer, and 3) application involving dry-type or cast coil transformers and some liquid filled. This paper will review these recent transformer failures due to primary circuit breaker switching transients to show the severity of damage caused by the voltage surge and discuss the common contributing factors. Next, switching transient simulations in the electromagnetic transients program (EMTP) will give case studies which illustrate how breaker characteristics of current chopping and re-strike combine with critical circuit characteristics to cause transformer failure. Design and installation considerations will be addressed, especially the challenges of retrofitting a snubber to an existing facility with limited space. For the cement industry, situations where circuit breaker induced switching transients are likely to damage transformers will be discussed. Finally, several techniques and equipment proven to successfully mitigate the breaker switching transients will be presented including surge arresters, surge capacitors, snubbers and these in combination.
Keywords :
EMTP; SF6 insulation; arresters; cables (electric); capacitors; cement industry; circuit breakers; coils; failure analysis; snubbers; switching transients; transformers; EMTP; SF-6 breaker; breaker characteristics; breaker switching transients; bus connection; cast coil transformers; cement industry; critical circuit characteristics; current chopping; electromagnetic transients program; primary circuit breaker switching transients; primary vacuum; short cable; snubber retrofitting; surge arresters; surge capacitors; switching transient simulations; transformer failure; transformer failures; transformers damage; voltage surge; Decision support systems; Economic indicators; EMTP simulations; RC snubbers; SF-6 breakers; Switching Transients; surge arresters; vacuum breakers;
Conference_Titel :
Cement Industry Technical Conference (CIC), 2013 IEEE-IAS/PCA
Conference_Location :
Orlando, FL
Print_ISBN :
978-1-4673-5552-0
DOI :
10.1109/CITCON.2013.6525287