    High-Frequency Model of the Power Transformer Based on Frequency-Response Measurements

  • Author

    Filipovic-Grcic, Dalibor ; Filipovic-Grcic, Bozidar ; Uglesic, Ivo

  • Author_Institution
    Electr. Eng. Inst., KONCAR, Zagreb, Croatia
  • Volume
    30
  • Issue
    1
  • fYear
    2015
  • fDate
    Feb. 2015
  • Firstpage
    34
  • Lastpage
    42
  • Abstract
    In this paper, a new high-frequency black-box model of the power transformer is presented for the calculation of transferred lightning overvoltages. The model is based on frequency-response analysis measurements and the application of four-terminal network theory. The computational verification of the presented model was successfully performed on a white-box transformer model in Electromagnetic Transients Program-Restructured Version software. The experimental verification was carried out on 130-kVA and 36-MVA three-phase power transformers. The presented calculation and measurement results confirm the validity of the proposed model for full and chopped lightning impulse voltages.
  • Keywords
    EMTP; frequency response; lightning; modelling; overvoltage; power transformers; electromagnetic transients program-restructured version software; four-terminal network theory; frequency-response analysis measurement; high-frequency black-box model; high-frequency transferred lightning overvoltage; lightning impulse voltage; three-phase power transformer; white-box transformer model; Frequency measurement; Lightning; Power transformer insulation; Surges; Voltage measurement; Windings; Fast Fourier transform (FFT); four-terminal network; frequency-response measurements; high-frequency transformer model; transfer function; transferred lightning overvoltages;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2014.2327061
  • Filename
    6839055