Abstract :
In this study measurements of temperature and airflow are used to compare three CFD models with different levels of modeling detail; a simplified model, a detailed model solved with reduced computational complexity and a full detailed model. This paper shows that the simplified model produces inaccurate results that would lead to incorrect conclusions about facility performance but the computationally simple model produces results that are good for conceptual design.
Keywords :
computational complexity; computational fluid dynamics; computer centres; flow measurement; temperature measurement; CFD models; airflow measurements; computational complexity; detailed data centre; facility performance; simple data centre; temperature measurements; Atmospheric modeling; Computational fluid dynamics; Computational modeling; Data models; Floors; Heating; Temperature measurement; CFD; Computational Fluid Dynamics; Experimental Comparison; Modeling Complexity; Simulation;