    The effect of fault states of the twelve-pulse rectifier during the recuperation

  • Author

    Dolecek, Radovan ; Mlynarik, L.

  • Author_Institution
    Dept. of Electr. & Electron. Eng. & Signalling in Transp., Univ. of Pardubice, Pardubice, Czech Republic
  • fYear
    2013
  • fDate
    16-17 April 2013
  • Firstpage
    27
  • Lastpage
    30
  • Abstract
    The paper deals with the fault states of twelve-pulse rectifier in traction substation of 3 kV DC traction system used at railways in the Czech Republic. The situation at diode breakdown of rectifier and at the same time recuperative traction vehicles in power supply section. The vehicle with recuperation can increase stress of elements in power supply system under certain conditions during fault states of rectifier. The simulation computer model was created for analysis of current waveforms in trolley line at this situation. The all simulations were done by program PSpice. The main goal is to analyze the endanger elements of power supply system and bring the recommendation for increasing of reliability of this mentioned power supply system.
  • Keywords
    electric breakdown; power distribution faults; rectifying circuits; semiconductor diodes; traction power supplies; Czech Republic; DC traction system; diode breakdown; fault state effect; power supply section; time recuperative traction vehicle; twelve pulse rectifier; voltage 3 kV; Electric breakdown; Integrated circuit modeling; Rail transportation; Rectifiers; Substations; Vehicles; Windings; Twelve-pulse rectifier; diode breakdown; recuperation; traction substation; transformer;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Radioelektronika (RADIOELEKTRONIKA), 2013 23rd International Conference
  • Conference_Location
    Pardubice
  • Print_ISBN
    978-1-4673-5516-2
  • Type

    conf

  • DOI
    10.1109/RadioElek.2013.6530883
  • Filename
    6530883