DocumentCode :
613420
Title :
Research on electromagnetic character of 500/220kV mixed-voltage quadruple-circuit transmission line
Author :
Weidong Liu ; Kun Liu ; Mingjiu Pan ; Gang Xu
Author_Institution :
Dept. of Econ. Res. Inst., Zhejiang Electr. Power Corp., Hangzhou, China
fYear :
2013
fDate :
5-8 May 2013
Firstpage :
227
Lastpage :
231
Abstract :
Electromagnetic environment is one of the key problems restricting the construction of quadruple-circuit transmission line on the same tower. In the paper, we use charge simulation method and current simulation method to calculate the electromagnetic character of 500/220kV mixed-voltage quadruple-circuit transmission line and analyze the influences to the surrounding environment. In the experiments, the electromagnetic field distribution near the ground(1.5m from the ground) of 500/220kV mixed-voltage quadruple-circuit transmission line of 3 typical tower types and 12 phase sequence arrangements are calculated, and from the results we can find out the advantages and disadvantages of the three tower types and optimal or worst phase sequence arrangements. Furthermore the impact of minimum conductor height to the ground on electromagnetic field distribution is also analyzed. Through the experiments it is able to be verified that the 500/220kv mixed-voltage quadruple-circuit transmission line is quite feasible, which provides powerful references for the construction of other mixed-voltage multi-circuit transmission line.
Keywords :
electromagnetic fields; poles and towers; power transmission lines; transmission line theory; charge simulation method; current simulation method; electromagnetic character; electromagnetic environment; electromagnetic field distribution; minimum conductor height; mixed-voltage multicircuit transmission line; mixed-voltage quadruple-circuit transmission line; phase sequence arrangements; tower; voltage 220 kV; voltage 500 kV; Conductors; Electric fields; Magnetic fields; Poles and towers; Power transmission lines; electromagnetic character; mixed-voltage on the same tower; phase sequence arrangement; quadruple-circuit transmission line on the same tower; transmission corridors;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Environment and Electrical Engineering (EEEIC), 2013 12th International Conference on
Conference_Location :
Wroclaw
Print_ISBN :
978-1-4673-3060-2
Type :
conf
DOI :
10.1109/EEEIC.2013.6549621
Filename :
6549621
Link To Document :
بازگشت