An optimal surge arrester for EHV air insulated stations utilizing high-gradient MO resistors
Author :
Stenstrom, L. ; Taylor, James ; Westerlund, H.
Author_Institution :
ABB AB High Voltage Components, Ludvika, Sweden
fYear :
2013
fDate :
2-5 June 2013
Firstpage :
201
Lastpage :
205
Abstract :
The use of high-gradient (HGR) MO resistors makes it possible to significantly reduce the length of surge arresters for air insulated substations (AIS). The optimal length would be to use HGR MO resistors which exactly fill up the necessary length needed to obtain a sufficient margin between arrester protection level and the voltage withstand of the housing. However, this would require a design with excellent thermal properties which could handle the increased power losses per unit length and higher temperature after energy absorption. This paper describes a surge arrester design in accordance with this concept. Furthermore, the requirements, type tests performed to verify the design and experience from a three and a half year field installation with supervision of the arrester leakage current are presented.
Keywords :
arresters; leakage currents; resistors; substation protection; EHV air insulated stations; air insulated substations; arrester leakage current; energy absorption; high-gradient MO resistors; surge arrester design; Arresters; Current measurement; Leakage currents; Resistors; Stress; Surges; AIS; MO resistor; condition monitoring; high-gradient; insulation withstand; surge arrester;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation Conference (EIC), 2013 IEEE
Conference_Location :
Ottawa, ON
Print_ISBN :
978-1-4673-4738-9
Electronic_ISBN :
978-1-4673-4739-6
Type :
conf
DOI :
10.1109/EIC.2013.6554233