• DocumentCode
    615701
  • Title

    Disturbance location in the Brazilian electric power system using synchrophasors

  • Author

    Zimmer, V. ; Decker, I.C. ; Agostini, Marcelo N.

  • Author_Institution
    LabPlan, Univ. Fed. de Santa Catarina, Florianopolis, Brazil
  • fYear
    2013
  • fDate
    15-17 April 2013
  • Firstpage
    1
  • Lastpage
    8
  • Abstract
    In this paper the results of a study on automatic detection, identification and location of systemic disturbances are described. The signal used for detection is the frequency obtained by phasor measurement units installed at Universities (SPMS MedFasee BT). Problems associated with frequency behavior are discussed, and three filtering methods are used in order to generate signals suitable for signaling detection of disturbances. The disturbances are classified in transient, loss of generation and load interruption. The estimation of the events location is performed by triangulation using Newton´s method. Actual events that occurred in the Brazilian Interconnected Power System are analyzed. The results show that SPMS allow the use of the described applications in real time operation.
  • Keywords
    phasor measurement; signal detection; Brazilian electric power system; automatic detection; disturbance location; real time operation; synchrophasors; systemic disturbances; Electronic mail; Global Positioning System; Kalman filters; Monitoring; Phasor measurement units; Power systems; Silicon compounds; Disturbance Location; MedFasee Project; PMU; frequency;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Innovative Smart Grid Technologies Latin America (ISGT LA), 2013 IEEE PES Conference On
  • Conference_Location
    Sao Paulo
  • Print_ISBN
    978-1-4673-5272-7
  • Type

    conf

  • DOI
    10.1109/ISGT-LA.2013.6554415
  • Filename
    6554415