Title :
Rogowski coil with an active integrator for measurement of switching impulse current
Author :
Limcharoen, Worrakan ; Yutthagowith, Peerawut
Author_Institution :
Electr. Eng. Dept., King Mongkut´s Inst. of Technol. Ladkrabang, Bangkok, Thailand
Abstract :
This paper presents design and construction of an impulse current measuring system based on a Rogowski coil with various types of integrators, a conventional RC integrator, a compensated RC integrator, and an active integrator. The developed measuring systems were designed for measurement of switching impulse current waveform used in a residual voltage test of arresters. The comparative measurement of the Rogowski coil with those integrators and non-inductive shunt resistor were carried out in an HV Laboratory. From the experiment results measured by the same Rogowski coil with various integrators show that all current measuring systems provide accurate front time. The Rogowski coil with the conventional RC and compensated integrators provide inaccurate measurement of inverse current peak and tail time. The Rogowski coil with the active integrator provides all fairly accurate waveform parameters when it was compared to the measured results by the non-inductive shunt resistor.
Keywords :
arresters; coils; electric current measurement; Rogowski coil; active integrator; arrester; compensated RC integrator; noninductive shunt resistor; residual voltage test; switching impulse current waveform measurement; Coils; Current measurement; Measurement uncertainty; Standards; Switches; Time measurement; Voltage measurement; Active integrator; Current measuring system; RC integrator; Rogowski coil; Switching impulse current;
Conference_Titel :
Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology (ECTI-CON), 2013 10th International Conference on
Conference_Location :
Krabi
Print_ISBN :
978-1-4799-0546-1
DOI :
10.1109/ECTICon.2013.6559578