• DocumentCode
    622218
  • Title

    Overcurrent relays coordination for commercial building

  • Author

    Aliman, O. ; Musirin, I.

  • Author_Institution
    Fac. of Electr. & Electron. Eng., Univ. Malaysia Pahang, Pekan, Malaysia
  • fYear
    2013
  • fDate
    3-4 June 2013
  • Firstpage
    608
  • Lastpage
    612
  • Abstract
    This paper presents an overcurrent relays coordination study for an 11 kV commercial building in southern Malaysia. Nevertheless, the actual study that covers the overcurrent relays, earth fault relays and earth leakage relays were executed by providing optimum and functionable relay settings prior to commissioning of the building. The calculated settings and proposed adjustment settings have been verified and simulated by ETAP power tool for predictive sequence and tripping time delay during fault. Based on the proven proposed settings, the coordination study been accepted by the concerned authority body and suggested for implementation accordingly.
  • Keywords
    building management systems; commissioning; earthing; overcurrent protection; power system faults; relay protection; ETAP power tool; building commissioning; commercial building; earth fault relays; earth leakage relays; functionable relay settings; optimum relay settings; overcurrent relays coordination; predictive sequence; southern Malaysia; tripping time delay; voltage 11 kV; Energy management; Integrated optics; Optical switches; Relays; TV; ETAP; Radial power system; STAR view of relay curves; over-current relays; protection; relay coordination;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering and Optimization Conference (PEOCO), 2013 IEEE 7th International
  • Conference_Location
    Langkawi
  • Print_ISBN
    978-1-4673-5072-3
  • Type

    conf

  • DOI
    10.1109/PEOCO.2013.6564620
  • Filename
    6564620